Fig 11. The best safety level: an earth-cage totally surrounding the house. This can be installed best by a specialist company. Connect the screening of the antenna cable to it.

The measures possibly taken by yourself are:

a. Install “earthing” (earth-electrodes). Here are two possibilities:

1. A vertical earth-electrode.
Best use for the electrode a copper water pipe, at least four meters long. You can drive it into the ground with a hammer. In many instances it also can be injected into the ground with the aid of a garden hose, connected to the water supply (figure 6).

2. A horizontal electrode in the ground.
Use for this preferably two twisted tinned copper wires, each with a surface of 6mm sq. (2.75mm diameter) and a length of at least 15 meters. Dig this conductor 60cm deep in the ground.

For safety reasons you may not use the safety-earth of the mains as lightning-ground.